Go top
Paper information

Contemporary electric energy meters testing under simulated nonsinusoidal field conditions

I. Diahovchenko, B. Dolník, M. Kanálik, J. Kurimský

Electrical Engineering Vol. 104, nº. 2, pp. 1077 - 1092

Summary:

The influence of distortions in voltage and current waveforms on state-of-the-art single-phase and three-phase power meters, commonly used in the utility power system of the Slovak Republic, was studied. A computer-controlled test system capable of generating nonsinusoidal voltages and currents and a reference power quality analyzer were used for this purpose. The results of the experiments on several revenue meters are presented. Some samples exhibited high errors under the tests, while the others operated within their tolerance limit. The overview of the current standards and previously published related studies on the operation of electric energy measuring equipment under determined and random nonsinusoidal conditions is given. The discussion including possible explanations of the phenomenon supervised under the conducted tests is provided.


Keywords: Electric energy meter · Energy measurement · Power quality · Nonsinusoidal voltage · Reactive energy · Definitions of power quantities


JCR Impact Factor and WoS quartile: 1,800 - Q3 (2022); 1,600 - Q3 (2023)

DOI reference: DOI icon https://doi.org/10.1007/s00202-021-01365-8

Published on paper: April 2022.

Published on-line: August 2021.



Citation:
I. Diahovchenko, B. Dolník, M. Kanálik, J. Kurimský, Contemporary electric energy meters testing under simulated nonsinusoidal field conditions. Electrical Engineering. Vol. 104, nº. 2, pp. 1077 - 1092, April 2022. [Online: August 2021]


pdf Preview
Request Request the document to be emailed to you.